NOTE: A brass external parallel thread to a brass internal parallel thread may be used, provided that the joint is welded or a suitable permanent quick-setting thread compound is used and a means of disconnection is provided immediately downstream. The combination of external and internal parallel threaded fittings is not permitted on gas installations except where no practical alternative is available. Image 1: Alternate arrangement using galvanised or brass tapered hex nipple. The following fittings should not be used:Ī parallel thread running nipple in steel or brass.Ī fitting with a taper thread one end and a parallel thread and socket the other, using a back nut and grommet to obtain a seal on the parallel thread. Clause 4.4 Prohibited Types of Joints and Fittings This information bulletin outlines the prohibited use of male parallel thread fittings on gas installations as detailed in Australian Standard AS/NZS 5601.1:2013 Gas installations – General installations.